IDD (Intellig. Diagn. Device)
Continuous on-line monitoring of bushing Power Factor/Tan Delta and capacitance via test tap. May also be used for hydrogen and/or moisture in oil via Doble or third party sensors.
User Benefits
- Continuous, cost-effective, assessment
- Eliminates forced outages by diagnosing the severity of the problem using expert system software
- Eliminates false alarms by advanced signal processing and field-proven algorithms
- Large amounts of data are processed by the IDD and the user only notified when necessary via detailed Alert messages
Specifications
- Inputs:
- Up to 12 bushings (4 sets of 3)
- Up to 3 Moisture-in-Oil sensors
- Up to 3 Dissolved gas sensor
- 2 via SCADA - Acknowledge and Reset Alerts
- Outputs: 4 via SCADA - Action Alert, Warning Alert, Information Alertand Self Monitoring
- Communications: Ethernet TCP/IP, RS485 (DNP3 and ASCII), Modem, RS232 (DNP3 and ASCII), Supervisory I/O
- Operating Environment: -40° to +65°C, 5 to 95% RH
- Power Supply: 100 to 280 VDC, 90 to 264 VAC
System Solutions
- Could combined with other transformer monitoring systems (e.g. Partial Discharge Monitoring)
-