Manual Control "LDcontrol" for HV Test Systems with Regulating Transformer (fixed frequency 50/60 Hz)

The application of "LDcontrol" is the manual control of HV power supplies with regulating transformer.

Applications

The application of "LDcontrol" is the manual control of HV power supplies with regulating transformer.

  • The control is qualified for the design of HV test fields which emergency stop and safety circuits meet the requirements of Performance Level d/e according to standard EN ISO 13849-1 and up to category 4 according to standard EN 954-1 respectively.
  • The switch-on/off procedure is in accordance with DIN EN 50191.
  • The control has been developed on the basis of DIN EN 61010-1 and DIN EN 61326-1

User Benefits

  • Ease of Use
  • Meets the latest safety standards
  • Remote interface terminal allows a later upgrade to an automated test system

Specifications

Common parameters:

  • Control of Main Switch and Operating Contactors
  • Overvoltage protection on secondary side and overcurrent protection on primary side with fast HV switch-off
  • Push-buttons for HV ON/OFF
  • Push-button Emergency Stop, additional Emergency Stop push-buttons may be connected
  • Push-buttons HV UP/DOWN
  • Connecting plug for the external safety circuit
  • Digital display for high voltage
    - Accuracy: 1 % from 10 to 100 % of nominal voltage (in
    accordance with DIN EN IEC 60060-1)
    - Displayed value: Peak/square root (standard), factory-
    provided pre-adjustement to peak value(optional)
  • Digital display for primary and secondary current
    - Accuracy: 5% from 10 to 100 % of nominal current
    - Displayed value: True RMS
  • Limit for secondary current and voltage adjustable via potentiometer
  • Potentiometer for speed adjustment of regulating transformer
  • LEDs for signaling current state of the control
  • Monitoring of the lower limit switch of the regulating transformer-contactor "HV on" can only be switched on in MIN-position of regulating transformer
  • Additional connector pins for external warning lamp (red/green)
  • Remote interface terminal allows a later upgrade to an automated test system
  • Mains: 115 V or 230 V, 50/60 Hz
  • Overall dimensions: 19"-plug-in module, 4 HE