M4100

Diagnostic test system for power apparatus condition assessment.

Applications

  • Loss angle (Power Factor/Tan δ), capacitance and inductance measurements on high voltage equipment

User Benefits

  • Easy, automated measurement
  • Accurate and powerful
  • Field-rugged and reliable
  • Immune to external interference due to line frequency modulation technique

Specifications

  • Voltage Range: 0 to12kV
  • Output Power: 3kVA
  • Output Current: 100mA continuous, 300mA >4 minutes, at 10kV
  • Output Frequency: 45 to 70 Hz
  • Current Measurement Range: 0 to 5A
  • Current Measurement Accuracy: ±1% of reading, ±1μA
  • Power Factor/Tan δ Range: 0 to 100% PF, 0 to 999.99% Tan δ
  • Power Factor/Tan δ Accuracy: ±0.04% PF/Tan δ of reading
  • Capacitance Range: 0 to 5μF
  • Capacitance Accuracy: ±0.5% of reading, ±1pF
  • Inductance Range: 10mH to 6H
  • Inductance Accuracy: ±0.5% of reading
  • Watts Range: 0 to 2kW
  • Watts Accuracy: ±2% of reading at 10kV, ±0.03% of VA, ±0.5mW
  • PC Communications: RS232 or USB
  • Operating Temperature: -20° to +50° C
  • Weight: 43kg

System Solutions

  • DTA Field software provides apparatus test templates and expert system analysis of results
  • DTA Web software provides hosted database function for test data

Accessories

  • TTR Capacitor for HV turns ratio measurements
  • M4110 for Leakage Reactance measurements
  • M4120 for measurements higher than 12kV (external source and reference)
  • M4140 for Capacitor Bank measurements (up to 100μF)
  • Type-C Resonating Inductor to extend charging current range for large test specimens - e.g., generators, motors and cables

Downloads

 

  • Prospect M4100