LDA-6
Multichannel-Acoustic Localisation of Partial Discharges inside Powertransformers
Applications
The LDA-6 was developed for acoustic localisation of dangerous Partial Discharges inside Powertransformers. Advanced algorithm allows a high precision localisation of the PartialDischargeSource. A graphical user interface visualise the spatial position of the Partial Discharge Source.
User Benefits
- precise localisation of dangerous Partial Discharges
- can combined with electrical Partial Discharge Measurement Devices LDS-6 or PD-Smart to increase the accuracy (electrical trigger)
- easy and fast installation of the acoustic sensors due to the magnetic fastener
- piezoelectric, acoustic sensorswith a small bandwith (noise-suppressionoutside the resonant frequency)
- up to 8 acoustic channels possible
- automatic calculation of the propagation velocity depending of the Oil-temperature
- graphical user interface for visualisation of the measurement results
Specifications
Power mains
- voltage 115-120 VAC or 230-240 VAC, 47-63 Hz
- power consumption 100 VA, approx. (max.)
Signal Stage
Sensor
- frequency: appr. 150kHz
- bandwith: appr. 8kH
Signal Input
- output bias voltage via input 20-28 VDC; internal adjusted
- max. output current via input 200 mA
- bias current fusibles cut-out 200 mA
- wave impedance 50 Ω
- max. input signal 10 VPeak
- overvoltage protection > 12 VPea
Signal Output to PC-DAQ card
- max. number of channels 8 (7)
- max. RF output signal 10 VPeak
- output center frequency approx. 150 kHz (by amplification "1"
- approx. 90 kHz (not by amplification "1")
- bandwidth approx. 100 kHz
- switcheable max. amplifications 1, 10, 50, 100
Testvoltage Stage
Signal Input
- max. input signal 50 VPeak
- overvoltage protection > 90 VPea
Signal Output to PC-DAQ card
- max. number of channels 1
- max. output signal 10 VPeak
- output frequency 0-300 Hz
Dimensions 342.1 mm * 132.5 mm * 326 mm (w*h*l)
Weight main unit approx. 6 kg,
Protection class IP 20
Environmental conditions
operating temperature: + 5 °C ... + 40 °C
storage temperature: -5 °C ...+60 °C
max. relative atmospheric humidity: 93 % at 30 °C max., not condensed
atmospheric pressure: standard pressure
Enlarge PictureDownload Picture
Enlarge PictureDownload Picture
Enlarge PictureDownload Picture
Enlarge PictureDownload Picture
-
04.12.09 LDIC renamed in DOBLE LEMKE
LDIC is renamed Doble Lemke to represent legacy ...
Read more
-
14.07.09 EuroDoble Colloquium 2009
Visit the EuroDoble Colloquium from 19. - 22. Okto...
Read more
-
26.06.09 UHF Partial Discharge Measurements
Trust in the experience and know-how of LDIC in th...
Read more