Diagnostic test system with built-in PC using Sweep Frequency Response Analysis (SFRA)
Applications
- Detection of core movement and winding deformation/displacement in transformers and reactors
User Benefits
- Easy-to-use software and test leads
- High accuracy and repeatability
- Field-rugged design
- Apparatus nameplate information stored with test data
Specifications
- Frequency Range: 10Hz to 25MHz.
- Default Range 20Hz to 2MHz.
- Output Voltage: 20V p-p at 50Ώ. Short-circuit protected.
- Number of Data Points: 1,000 (Default), up to 1,800 (Extended Range)
- Dynamic Range: >90dB
- Repeatability: ±1dB to -80dB
- Built-in PC
- Operating Environment: 0 to 50° C, 0 to 95% RH
- Weight: 10kg
- Test Leads: Integrated 3-lead system in single cable set, 18m length
-
04.12.09 LDIC renamed in DOBLE LEMKE